X20SO6300 B&R X20 PLC SYSTEM I/O Module 6 Safe Digital Outputs With 0.2 A

Categories B&R Automation Plc
Brand Name: B&R
Model Number: X20SO6300
Certification: COC
Place of Origin: Austria
MOQ: 1EA
Price: USD
Payment Terms: T/T
Supply Ability: 10EA
Delivery Time: 3-5 DAYS
Product Name: B&R
Product Model: X20SO6300
Product Type: I/O module
Internal I/O: 1.4 W
Voltage range: 24 VDC -15% / +20%
Warranty: 1 Year
  • Haven't found right suppliers
  • Our buyer assistants can help you find the most suitable, 100% reliable suppliers from China.
  • And this service is free of charge.
  • we have buyer assistants who speak English, French, Spanish......and we are ready to help you anytime!
Submit Buying Request
  • Product Details
  • Company Profile

X20SO6300 B&R X20 PLC SYSTEM I/O Module 6 Safe Digital Outputs With 0.2 A

X20SO6300 B&R X20 PLC SYSTEM I/O Module 6 Safe Digital Outputs With 0.2 A
MATERIAL NUMBER:

X20SO6300

DESCRIPTION:
  • 6 safe digital outputs with 0.2 A
  • Source circuit
  • Output type B
  • Integrated output protection

This module is equipped with 6 safe digital outputs. The nominal output current is 0.2 A.

The module can be used for controlling actuators in safety-related applications up to PL e or SIL 3.

The outputs are designed using semiconductor technology so that the safety-related characteristics do not depend on the number of operating cycles. The "high-side high-side" variant (output type B) is required for actuators with reference potential (e.g. Enable inputs on frequency inverters). It is important to observe the special notices for the cabling in this case. Safe digital output channels provide protection against automatic restart when network errors occur.

This module is designed for X20 12-pin terminal blocks.

Short description
I/O module6 safe type B1 digital outputs, 24 VDC, 0.2 A, OSSD <10 µs
General information
B&R ID code0xB815
System requirements
Automation Studio3.0.81.15 or later
Automation Runtime3.00 or later
SafeDESIGNER2.70 or later
Safety Release1.2 or later
mapp Technology Packagemapp Safety 5.7.0 or later
Status indicatorsI/O function per channel, operating state, module status
Diagnostics
Module run/errorYes, using LED status indicator and software
OutputsYes, using LED status indicator and software
Blackout mode
ScopeModule
FunctionModule functionality
Standalone modeNo
Max. I/O cycle time1 ms
Power consumption
Bus0.32 W
Internal I/O1.4 W
Additional power dissipation caused by actuators (resistive) [W]1.128
Electrical isolation
Channel - BusYes
Channel - ChannelNo
Certifications
CEYes
Functional safetycULus FSPC E361559
Energy and industrial systems
Certified for functional safety
ANSI UL 1998:2013
Functional safetyIEC 61508:2010, SIL 3
EN 62061:2013, SIL 3
EN ISO 13849-1:2015, Cat. 4 / PL e
IEC 61511:2004, SIL 3
Functional safetyEN 50156-1:2004
ATEXZone 2, II 3G Ex nA nC IIA T5 Gc
IP20, Ta (see X20 user's manual)
FTZÚ 09 ATEX 0083X
ULcULus E115267
Industrial control equipment
HazLoccCSAus 244665
Process control equipment
for hazardous locations
Class I, Division 2, Groups ABCD, T5
DNVIn preparation
EACYes
KCYes
Safety characteristics
EN ISO 13849-1:2015
CategoryCat. 3 if parameter "Disable OSSD = Yes - Warning",
Cat. 4 if parameter "Disable OSSD = No"
PLPL d if parameter "Disable OSSD = Yes - Warning",
PL e if parameter "Disable OSSD = No"
DC>60% if parameter "Disable OSSD = Yes - Warning",
>94% if parameter "Disable OSSD = No"
MTTFD2500 years
Mission timeMax. 20 years
IEC 61508:2010,
IEC 61511:2004,
EN 62061:2013
SIL CLSIL 2 if parameter "Disable OSSD = Yes - Warning",
SIL 3 if parameter "Disable OSSD = No"
SFF>60% if parameter "Disable OSSD = Yes - Warning",
>90% if parameter "Disable OSSD = No"
PFH / PFHd
Per channel<1*10-10
openSAFETY wiredNegligible
openSAFETY wireless<1*10-14* Number of openSAFETY packets per hour
PFD<2*10-5
Proof test interval (PT)20 years
I/O power supply
Nominal voltage24 VDC
Voltage range24 VDC -15% / +20%
Integrated protectionReverse polarity protection
Safe digital outputs
Quantity6
VariantFET, 2x positive switching, type B1, output level readable
Nominal voltage24 VDC
Nominal output current0.2 A
Total nominal current1.2 A
Output protectionSee section "Inrush current behavior for output channels".
Braking voltage when switching off inductive loadsMax. 45 VDC
Error detection time1 s
Insulation voltage between channel and bus500 Veff
Peak short-circuit currentSee section "Inrush current behavior for output channels".
Leakage current when the output is switched off<100 µA
RDS(on)4.7 Ω
Switching voltageI/O power supply minus voltage drop due to RDS(on)
Max. switching frequencySee section "Inrush current behavior for output channels".
Test pulse lengthMax. 10 µs
Max. capacitive load100 nF
Current on loss of ground
IOUT<100 µA
IGND<70 mA
Operating conditions
Mounting orientation
HorizontalYes
VerticalYes
Installation elevation above sea level0 to 2000 m, no limitation
Degree of protection per EN 60529IP20
Ambient conditions
Temperature
Operation
Horizontal mounting orientation0 to 60°C
Vertical mounting orientation0 to 50°C
DeratingSee section "Derating".
Storage-40 to 85°C
Transport-40 to 85°C
Relative humidity
Operation5 to 95%, non-condensing
Storage5 to 95%, non-condensing
Transport5 to 95%, non-condensing
Mechanical properties
NoteOrder 1x safety-keyed terminal block separately.
Order 1x safety-keyed bus module separately.
Pitch25+0.2mm
Quality X20SO6300 B&R X20 PLC SYSTEM I/O Module 6 Safe Digital Outputs With 0.2 A wholesale
Send your message to this supplier
 
*From:
*To: Joyoung International Trading Co.,Ltd
*Subject:
*Message:
Characters Remaining: (0/3000)
 