| Sign In | Join Free | My insurersguide.com |
|
| Categories | 5G Network Equipment |
|---|---|
| Brand Name: | Eaton |
| Model Number: | ups system |
| Certification: | CE, RoHS |
| Place of Origin: | Hubei, China |
| MOQ: | 1 Piece |
| Price: | Negotiable |
| Payment Terms: | T/T, L/C |
| Supply Ability: | 10000 Pieces/Month |
| Delivery Time: | within 10 days of payment |
| Packaging Details: | carton & PVC packaging |
| Power Rating: | 8-60 kW |
| Topology: | Double conversion on demand |
| Frequency: | 50/60 Hz |
| Efficiency: | Up to 98% |
| Configuration: | Rack mount |
| Voltage: | 208 Vac/400 Vac |
Eaton Blade UPS Power System Scalable Double-Conversion Backup Power
Product Snapshot
| Power Rating | 8-60 kW |
| Voltage | 208 Vac and 400 Vac models |
| Frequency | 50/60 Hz |
| Topology | Double conversion on demand |
| Efficiency | Up to 98% |
| Configuration | Rackmount |
| Product Series | Eaton |
Technical Specifications
| GENERAL | |
| Power rating | 12 kW per UPS module |
| Efficiency | up to 98% |
| Heat dissipation | 371W/1266 BTU/hr at 100% rated load |
| Cooling | Fan cooled, temperature microprocessor monitored; front air entry, rear exhaust |
| Audible noise, normal operation | <60 dBA at 1 meter |
| OPERATION | |
| Nominal Input Voltage | 220/230/240 |
| Input Voltage Range | +15%, -20% |
| Operating Frequency | 50 Hz Nominal (adjustable limits +_ 0.01 Hz to +_ 3Hz |
| Nominal Output Voltage | 220/230/240 |
| Output Voltage Regulation | ± 3% for input voltages of +15% to -20% |
| Output Voltage Waveform | Sine wave |
| Output Voltage THD | 5% or less at rated kW load |
| Overload Capacity | 150% surge and 125% for10 min. on line, 150% surge and 110% for 10 minutes on inverter |
| Transfer Time | 0 ms |
| Lightning, Surge & Noise Protection | 2000:1 spike attenuation using ANSI/IEEE C62.41 and C62.45 Category
A and Category B tests. Common Mode – >120 dB. Normal Mode – >60dB |
| Efficiency | 85 / 88 / 91 / 90 |
| Safety Certification | UL, CSA (cUL), Complies with European Low Voltage Directive 73/23/EEC |
| EMI Compliance | FCC Class A, Complies with European Electromagnetic Compatibility Directve 89/336/EEC |
| Testing Standards | ANSI/EEE C62.41 (1991); ANSI/EEE C62.45 (2002); EN62040-2 |
| Communication | RS-232 serial port (DB-25), plus contact closures |
| ENVIROMENTAL | |
| Operating Temperature | 0 to 40° C |
| Storage | -20° C to +60° C |
| Relative Humidity | 0 to 95% without condensation |
| Audible Noise at 1m | 47 / 49 / 51 / 51 |
| Altitude | 3, 050m (10,000 ft.) maximum |
1. Due to continuous product improvements, program specifications are subject to change without notice.
Industries & Applications
Both scalable and modular, the rackmount EATON BladeUPS Power System expands power protection from 8 to 60 KW in a single 19-inch rack while reducing energy and cooling costs for your industrial UPS system or commercial UPS system.
The EATON Blade UPS is purpose-engineered for demanding applications require extraordinary levels of reliability such as 911 centers, global military installations, marine vessels, and other mission-critical applications that demand an industrial UPS system that is also a high quality power backup system for sensitive equipment. Applications include but are not limited to:
Police & fire emergency call centers
Military applications
“Lights-out” or “dark factory” manufacturing
Large data centers or IT systems
Critical network switching & processing equipment
Large-scale PLC controls

|